Main Features:
Frequency: Hz 50
Voltage: V 230
Power factor: cos ϕ 0.8
Phase and connection: Single
Power Rating:
Standby power LTP kVA 10.8
Standby power LTP kW 9.7
Prime power PRP kVA 10.0
Prime power PRP kW 9.0
Ratings definition (According to standard ISO8528 1:2005)
PRP - Prime Power:
It is defined as being the maximum power which a generating set is capable of delivering continuously
whilst supplying a variable electrical load when operated for an unlimited number of hours per year under
the agreed operating conditions with the maintenance intervals and procedures being carried out as
prescribed by the manufacturer. The permissible average power output over 24 h of operation shall not
exceed 70 % of the prime power.
LTP - Limited-Time running Power:
It is defined as the maximum power available, under the agreed operating conditions, for which the
generating set is capable of delivering for up to 500 h of operation per year (whose no more than 300 for
continuative use) with the maintenance intervals and procedures being carried out as prescribed by the
manufacturers. No overload capability is available.
10KVA PERKINS SILENT DIESEL GENERATOR
Engine specifications:
Engine manufacturer: Perkins
Model: 403D-11G
[50Hz] Exhaust emission level: Unregulated
Engine cooling system: Water
Nr. of cylinder and disposition: 3 in line
Displacement: cm³ 1131
Aspiration: Natural
Speed governor: Mechanical
Prime gross power PRP kW 9.0
Maximum gross power LTP kW 9.7
Oil capacity: l 4.9
Coolant capacity: l 5.2
Fuel: Diesel
Specific fuel consumption @ 75% PRP: g/kWh 258
Specific fuel consumption @ PRP: g/kWh 252
Starting system: Electric
Starting engine capability: kW 1.1
Electric circuit: V 12Engine Equipment
Standards
The above ratings represent the engine performance capabilities to conditions
specified in ISO 8528/1, ISO 3046/1:1986, BS 5514/1
Fuel system
Rotary type pump
Lube oil system
Wet steel sump with filler and dipstick
Filter
• Fuel filter
• Air filter
• Oil filter
Cooling system
• Mounted radiator
• Thermostatically-controlled system with belt driven coolant pump and pusher fanKindly indicate your location or provide physical address so delivery can be quoted to you accordingly. Thank you